B747-400 Electrical Generators
Thread Starter
Join Date: Jan 1999
Location: London, UK
Posts: 144
Likes: 0
Received 0 Likes
on
0 Posts
B747-400 Electrical Generators
Hi,
How much power does each electrical generator on the B747-400 produce?
I believe they're rated at 90 kVA; is that equivalent to 90 kW?
Z.
How much power does each electrical generator on the B747-400 produce?
I believe they're rated at 90 kVA; is that equivalent to 90 kW?
Z.
Join Date: Oct 2004
Location: Europe
Posts: 30
Likes: 0
Received 0 Likes
on
0 Posts
I'm far from being an expert on electricity - in fact, I'm just a pilot...
But this is the way I understood it:
Watts=(Volt x Amps) x power factor
REAL Power: Watts
APPARANT Power: VA
A three-phase generator has a "Power factor" (cos phi) of 0.8 - so as "catchup" said the (k)VA is always higher.
Hopefully someone can explain it better!
But this is the way I understood it:
Watts=(Volt x Amps) x power factor
REAL Power: Watts
APPARANT Power: VA
A three-phase generator has a "Power factor" (cos phi) of 0.8 - so as "catchup" said the (k)VA is always higher.
Hopefully someone can explain it better!
Join Date: Jun 2004
Location: Vilha Abrao
Posts: 507
Likes: 0
Received 0 Likes
on
0 Posts
Yeah, it has to do with the "phase-shift" of a three-phase generator.
Good enough for us pilots.
regards
Yeah, 90 kVA is correct. Six of them....
Good enough for us pilots.
regards
Yeah, 90 kVA is correct. Six of them....
Last edited by catchup; 30th Nov 2004 at 09:34.
Usual disclaimers apply!
Join Date: Nov 1999
Location: EGGW
Posts: 843
Likes: 0
Received 0 Likes
on
0 Posts
Er not quite! the main gennies and apu gennies cannot be pararrelled. Indeed, even the apu gennies cannot be pararrelled as the split system breaker will open.
So it would be 90KVA *4 (main gennies all pararrelled) or apu 90KVA *2 (split between busses 1+2 and 3+4)
Mind you, if you were pulling that much load.....there might be a problem
So it would be 90KVA *4 (main gennies all pararrelled) or apu 90KVA *2 (split between busses 1+2 and 3+4)
Mind you, if you were pulling that much load.....there might be a problem
Join Date: Aug 2003
Location: Canada
Posts: 79
Likes: 0
Received 0 Likes
on
0 Posts
An AC circuit has three types of loads: Pure resistance, inductive and capacitive. True power (P) is the power consumed by the resistance elements only, and as someone pointed out P=IR. That would be exactly the same a calculating the power of a DC circuit. However, the apparent power (U) takes into account all resistances plus the inductvive and/or capacitive reactances. (reactance is kinda the same as resistance) A circuit can be predominantly inductive or predominantly capacitive. When you sum all the inductive and capacitive reactances, you end up with either a capacitive reactive power or an inductive reactive power.
To arrive at the apparent power (U), you must vectorially add the true power (P) and the reactive power (Q) (inductive or capacitive). Apparent power is always greater than or equal to reactive power. If you can imagine a graph, reactive power increases along the +ve x-axis, and inductive power goes up along the +ve y-axis and capacitive power goes down along the -ve y-axis. Apparent power points either up and to the right (inductive) or down and to the right (capacitive).
True power (P) is measured in watts (W). Apparent power (U) is measured in volt-amps (VA) and reactive power (Q) is measured in volt-amps-reactive (VAR).
The power factor (PF) is the ratio of true power to apparent power. PF=P/U. It is basically the circuits efficiency. It is not a costant value (like 0.8) but depends on the phase angle. PF=cosine (phase angle). PF=1 for purely resistive circuits, and PF=0 for purely reactive circuits. You might be thinking of the RMS voltage/current which is 0.707 times the maximum voltage/current.
To arrive at the apparent power (U), you must vectorially add the true power (P) and the reactive power (Q) (inductive or capacitive). Apparent power is always greater than or equal to reactive power. If you can imagine a graph, reactive power increases along the +ve x-axis, and inductive power goes up along the +ve y-axis and capacitive power goes down along the -ve y-axis. Apparent power points either up and to the right (inductive) or down and to the right (capacitive).
True power (P) is measured in watts (W). Apparent power (U) is measured in volt-amps (VA) and reactive power (Q) is measured in volt-amps-reactive (VAR).
The power factor (PF) is the ratio of true power to apparent power. PF=P/U. It is basically the circuits efficiency. It is not a costant value (like 0.8) but depends on the phase angle. PF=cosine (phase angle). PF=1 for purely resistive circuits, and PF=0 for purely reactive circuits. You might be thinking of the RMS voltage/current which is 0.707 times the maximum voltage/current.
Last edited by GearDoor; 30th Nov 2004 at 17:54.
Join Date: Oct 2001
Location: The Beautiful South
Posts: 199
Likes: 0
Received 0 Likes
on
0 Posts
Milt......
Yes, Engine at Gnd Idle the AC Generators provide full power.
BTW there is no seperate CSD unit, as IDGs ( Intergrated Drive Generator ) are fitted.
Normal AC generators fitted on the APU.
Yes, Engine at Gnd Idle the AC Generators provide full power.
BTW there is no seperate CSD unit, as IDGs ( Intergrated Drive Generator ) are fitted.
Normal AC generators fitted on the APU.